B&R X20DI4371 is a high-performance digital input module for B&R X20 distributed I/O automation system. It provides 4 channels of 24 VDC sink digital inputs with 3-wire sensor connection design, and each channel doubles as a 16-bit event counter supporting up to 1 kHz pulse input. The module features configurable input filter, galvanic isolation between field channels and X2X Link backplane bus, plus built-in short-circuit protection for sensor power supply. Front LED indicators display module status and individual channel signal state. It communicates with X20 CPU via X2X Link, widely used for sensor signal acquisition, pulse counting and industrial spare replacement.

Product Details
The B&R X20DI4371 belongs to B&R X20 digital I/O module family, designed for discrete signal capture and pulse measurement tasks in X20 automation stations. It mounts directly on the X20 backplane and exchanges process and counter data with the main X20 controller through the X2X Link bus, offering flexible signal acquisition for proximity sensors, photoelectric switches and pulse encoders.
This module has 4 sink-type digital inputs complying with EN 61131-2 Type 1 standard. The nominal input voltage is 24 VDC, and typical input current is 3.75 mA at 24 VDC. It adopts 3-wire connection which can supply 24 VDC and GND for field sensors, and the sensor power output comes with short-circuit protection. The switching threshold is defined as low level below 5 VDC and high level above 15 VDC, ensuring stable signal recognition under noisy factory environments.
The input filter combines hardware and software settings. The hardware filter is fixed at ≤100 µs, while the software filter can be adjusted from 0 ms to 25 ms with 0.2 ms step increments, allowing users to suppress contact bounce or high-frequency interference according to field conditions. Each of the four input channels integrates a 16-bit event counter, supporting rising edge, falling edge or dual-edge trigger evaluation. The maximum counter frequency reaches 1 kHz when the software filter is disabled, suitable for low-speed pulse counting and event capture.
Galvanic isolation of 500 V_{eff} is implemented between field input channels and the X2X Link backplane bus to isolate common-mode voltage and electrical noise, protecting the PLC backplane from field-side disturbances. Wiring is completed by X20TB12 12-pin terminal block for simple field installation and maintenance. Front panel LED indicators continuously show module run status, fault alarm and real-time signal status of each channel, helping technicians quickly locate signal and wiring issues during commissioning and routine maintenance.
It supports DIN rail horizontal or vertical mounting with IP20 protection rating for cabinet installation. It holds CE, UKCA, cULus, ATEX Zone 2, HazLoc Class I Division 2, DNV, LR, ABS and KC certifications, applicable for general factory automation, hazardous area equipment and marine automation systems. It can be freely combined with other X20 analog, digital and communication modules to build customized distributed I/O solutions.
Typical applications include packaging machinery, material handling systems, textile machines, conveyor lines and plastic processing equipment. It serves as digital signal acquisition unit, pulse counter module and spare maintenance component for B&R X20 automation platforms.

Product Parameters
Model: X20DI4371Brand: B&R AutomationProduct Type: X20 4-channel Digital Input Module with Event CounterCompatible System: B&R X20 distributed I/O systemNumber of Inputs: 4Input Type: Sink, EN 61131-2 Type1Nominal Supply Voltage: 24 VDC (-15% / +20%)Typical Input Current: 3.75 mA @24 VDCInput Resistance: 6.4 kΩSwitching Threshold: Low <5 VDC; High >15 VDCConnection Type: 3-wire connections, provides sensor 24VDC and GNDInput Filter: Hardware ≤100 µs; Software configurable 0~25 ms (0.2ms step)Counter Function: 4 x 16-bit event counters, max 1 kHz (filter off)Counter Trigger: Configurable rising / falling / both edgesIsolation: 500 V_{eff} galvanic isolation between channel and X2X Link busSensor Supply Protection: Short-circuit protection, max 0.5A summation currentDiagnostic Indicators: Front LED for module run status, error, individual channel input statusConnection Terminal: X20TB12 12-pin terminal blockPower Consumption: Bus:0.1 W; Sensor supply max.12 WMounting: DIN rail mount, horizontal / vertical installationOperating Temperature: Horizontal: -25 ~ 60°C; Vertical: -25 ~ 50°CStorage / Transport Temperature: -40 ~ 85°CRelative Humidity: 5 ~ 95%, non-condensingMax Installation Altitude: 4000 m (temperature derating above 2000m)Certifications: CE, UKCA, cULus, ATEX Zone 2, HazLoc Class I Division 2, DNV, LR, ABS, KCProtection Class: IP20Software Support: B&R Automation StudioApplication: Digital sensor signal acquisition, pulse and event counting, industrial automation spare replacement
Tags: B&R X20DI4371 B&R X20 digital input module X20DI4371 I/O module B&R X20 pulse counter