Products Introduction

Brief Introduction
The ICS TRIPLEX T8846 is a SIL 3 rated speed input FTA, specially designed to work with T8442 TMR speed monitor module in Trusted safety instrumented systems. It provides signal conditioning, sensor power supply and field termination for speed probes of rotating machinery. It supports both passive magnetic speed pickups and active speed sensors, with three galvanically isolated machine groups to avoid cross-group fault propagation. DIN rail mounting and field-replaceable fuses simplify on-site wiring and maintenance for turbine and compressor overspeed protection loops.

Product Details
The T8846 SIFTA is a DIN rail mounted termination assembly that serves as the field interface for T8442 speed monitor module. It integrates nine speed input channels, divided into three independent groups of three channels each, to support up to three rotating machine trains. Each group features separate field power supply and signal isolation, limiting common-cause faults between different machine groups. It is compatible with passive inductive speed probes, open-collector and totem-pole active speed sensors, and can supply power for active probes directly. Built-in fuses for each channel are field replaceable without removing the whole assembly. It connects to T8442 module via TC-801 dedicated I/O cable. It works together with T8891 SOFTA output FTA to complete the full turbomachinery overspeed protection solution. It meets IEC 61508 SIL 3 requirements for critical rotating equipment safety protection.

Specifications
Brand: ICS TRIPLEX
Model: T8846
Type: Speed Input Field Termination Assembly (SIFTA)
Safety Standard: IEC 61508 SIL 3
Compatible Module: T8442 TMR speed monitor module
Channel Configuration: 9 speed input channels, 3 independent machine groups (3 channels per group)
Sensor Support: Passive magnetic / inductive probes, open-collector, totem-pole active speed sensors
Mounting: Standard DIN rail mounting
Connection Cable: TC-801
Field Supply Range: 18–32VDC
Max Field Current per Group: 1A
Feature: Galvanic isolation between groups, field replaceable fuses, passive signal conditioning
Operating Temperature: 0°C to +60°C
Storage Temperature: -25°C to +70°C
Relative Humidity: 10%–95%, non-condensing
Weight: 0.75kg
Certification: TÜV, CE, UL, ATEX, IECEx
Tags: ICS TRIPLEX T8846 T8846 SIFTA T8846 speed input FTA Trusted T8442 termination assembly turbine overspeed probe interface