Products Introduction
Content Introduction
The ProSoft PLX51-DF1-MSG is an industrial messaging gateway for DF1 serial protocol and EtherNet/IP communication. It connects legacy Allen‑Bradley SLC500, MicroLogix, PLC-5 and DF1 radio modem devices to modern Logix EtherNet/IP controllers. It is widely used in wastewater treatment, factory automation, remote radio SCADA and legacy PLC migration projects. It is a reliable spare part for DF1 radio messaging and serial-to-EtherNet/IP message transmission.
Product Details
This DIN-rail mounted gateway is equipped with one 10/100 Mbps EtherNet/IP port and one isolated RS232 DF1 serial port. It supports DF1 full-duplex, half-duplex and DF1 radio modem modes with store-and-forward function. It adopts direct-to-tag technology to simplify Logix tag data mapping, and supports redundant ControlLogix system deployment.
It is configured via PLX50 Configuration Utility. Built-in DF1 packet analyzer helps diagnose serial communication faults. It holds UL/cUL Class I Division 2 and ATEX Zone 2 certifications. Front panel LEDs indicate power, fault, network and serial communication status. Rugged industrial hardware ensures stable performance in remote field and radio SCADA sites.

Product Parameters
| Parameter | Specification |
|---|---|
| Model | PLX51-DF1-MSG |
| Series | PLX51 DF1 Messaging Gateway |
| Rated Power | 10–36 VDC wide range |
| Interface | 1×10/100M EtherNet/IP, 1×isolated RS232 DF1 |
| Power Supply | External 10–36 VDC |
| Protection Class | IP20 |
| Communication | DF1 serial, DF1 radio modem, EtherNet/IP |
| Mounting | DIN rail mounting |
| Operating Temperature | -30°C to 70°C |
| Relative Humidity | 5% to 95%, non-condensing |
| Weight | Refer to manufacturer datasheet |